The AEC2323 explosion-proof audible-visual alarm is a small audible-visual alarm applicable to zone-1 and 2 hazardous areas and class-IIA, IIB, IIC explosive gas environment with a temperature class of T1-T6.
The product has a stainless steel enclosure and a red PC lampshade. It is characterized by high intensity, impact resistantance, and high explosion-proof grade. Its LED luminescent tube is characterized by highlight, long service life and non-maintenance. With a G3/4’’ pipe thread (male) electrical interface design, it is easier to be connected to other devices to give audible-visual alarms at dangerous sites.
The product has a unique sound control function. As it is used in combination with an ACTION gas detector, its sound can be eliminated by using the detector’s calibration remote controller or a supporting controller. After sound elimination, it can still give audible alarms.
Operating voltage: DC24V±25%
Operating current: <50mA
Light intensity: 2400±200mcd
Sound intensity: >93dB@10cm
Explosion-proof sign: ExdⅡCT6 Gb
Protection grade: IP66
Electrical interface: NPT3/4"pipe thread (male)
Material: Stainless steel